Thank you for visiting nature.com. You are using a browser version with limited support for CSS. To obtain the best experience, we recommend you use a more up to date browser (or turn off compatibility mode in Internet Explorer). In the meantime, to ensure continued support, we are displaying the site without styles and JavaScript.

Scientific Reports volume  14, Article number: 1513 (2024 ) Cite this article Suspension Disc Insulator

Partial discharge (PD) could lead to the formation of small arcs or sparks within the insulating material, which can cause damage and degradation to the insulator over time. In ceramic insulators, there are several factors that can cause PD including manufacturing defects, aging, and exposure to environmental conditions such as moisture and temperature extremes. As a result, detecting and monitoring PD in ceramic insulators is important for ensuring the reliability and safety of electrical systems that rely on these insulators. In this study, acoustic emission technique is introduced for PD detection and condition monitoring of defective ceramic insulators. A sequence of data processing techniques is performed on the captured signals to extract and select the most significant signatures for classification of defects in insulator strings. Artificial neural network (ANN) has been used to build an intelligent classifier for easily and accurately classification of defective insulators. The overall recognition rate of the classifier was obtained at 96.03% from discrete wavelet transform analysis and 88.65% from fast Fourier transform analysis. This obtained result indicates high accuracy and performance classification. The outcomes of ANN were verified by SVM and KNN algorithms.

Utilities have used outdoor insulators to support overhead lines at both transmission and distribution voltage ratings. These insulators serve a crucial function of insulating the high voltage transmission line from the steel tower1. Due to their nature of operation in overhead transmission and distribution lines, outdoor ceramic insulators are subjected to various defects under operating and environmental conditions. One of these defects is the expansion of cement which can form cracks in the insulator, and this expansion can be accelerated under wet conditions leading to insulator failure2. As a result, Cherney and Hoton3 introduced water expansion tests on the used cement to ensure its quality when assembled with the insulator. Also, erosion and corrosion of pin and cap hardware in the insulator is another defect that can occur due to the salt solution formation on the insulator surface. Under wet atmospheric conditions, the formed salt solution may lead to a loss in cross-section area and mechanical strength in the insulator pin leading to the overhead conductor dropping4. Furthermore, contamination flashover is the main problem of overhead insulators5,6,7,8. Contaminants, such as salts, chemical particles, dust, sand, etc., can accumulate on the surface of the insulator. In wet conditions, the pollution surface layer is converted into a conductive layer and the leakage current passes through these layers on the insulator surface causing heating of that layer. Dry bands are then formed and discharges can continue until the insulator flashover and outage of the power line occur9. Ceramic insulators may be broken and punctured due to the occurrence of overvoltages from the lightning on the transmission line4. Also, during the manufacturing process, very small internal voids or cracks may be developed within the insulator10,11. These voids may cause continuous discharges under operating conditions, leading to insulator failure. As a result, PD growth measurement is the most significant indicator of all the above mentioned defects that occurred for the overhead insulators12. Consequently, many researchers have introduced various methods to evaluate the insulators’ condition based on PD signatures1. Many detection techniques, based on both electrical and non-electrical methods, have been introduced for the detection, analysis, and evaluation of PD activities13,14,15,16,17,18,19. Each technique has benefits and drawbacks, and one may be better than the other depending on the application. A brief overview of the widely used techniques for monitoring the condition of the overhead line insulators will be provided in Fig. 120.

Measurement and detection techniques of partial discharge.

In order to create a classifier that can distinguish between and identify faults, partial discharges, defects, or degradation, a number of factors have been manually collected from recorded patterns or signals over time21. While the process has become somewhat automated, the need for experts to manually select the features presents a challenge, as different features may lead to different outcomes. This relying on selected features manually can adversely affect the classifier's performance.

Deep learning enables the integration of feature selection with the learning process, thereby automating the entire process. In the realm of applications of high voltage, the primary objective has been to localize or classify faults, defects, or partial discharges that could occur in high voltage equipment, or to detect the deterioration of insulating materials. Classification involves differentiating between various sources of faults, defects, partial discharges, or levels of degradation. Artificial intelligence techniques that are applied to classify the condition of insulators hold great promise, as defects could be automatically fixed out of pattern recognition22. Deep learning techniques can be utilized to detect the presence of a fluctuating number of missing discs in transmission lines consisting of chain insulators23. The main challenge in using computer vision to detect insulator failures is the infrequency of such failures. As a result, training a network to recognize specific conditions becomes challenging due to the limited dataset available23. However, applying engineering constraints to datasets captured through inspections could enhance the model's accuracy, resulting in an accuracy rate of up to 92.86%, as demonstrated in24.

Many techniques of artificial intelligence have been developed for predicting the stability of smart grids25,26,27,28,29. Furthermore, researchers have shown the widespread utilization of these techniques such as artificial neural network (ANN)30,31,32, support vector machine (SVM)33, fuzzy logic (FL)34, K-means clustering35, and hidden markov model (HMM)36 in addressing electrical power system and high voltage engineering issues37,38. Intelligent systems can improve the reliability of the transmission and distribution power system, reduce costs, and reduce human effort by facilitating effective assessment of the state and performance of outdoor insulators during voltage operation39. In their study, Salem et al.40 utilized insulator diameter, height, creepage distance, form factor, and equivalent salt deposit density (ESDD) as input parameters to train a model that combined the Adaptive neuro fuzzy inference system (ANFIS) with ANN. Also, by establishing correlations between leakage current and weather conditions, A. Din et al.41 used the SVM technique to evaluate the leakage current for outdoor insulators. In another work, Saranya et al.42 put forward a novel approach for assessing the status and performance of outdoor insulators, which involves recognizing the arc faults of insulators through measurements of phasor angle.

In this current work, the detection technique of acoustic emission is used for the detection of PD signatures resulting in artificial defects in ceramic outdoor insulators. A series of advanced signal processing techniques are performed on the captured signals from the experimental section to extract and select the most significant features to be as input data for the proposed classifier. Accordingly, an artificial neural network (ANN) analysis is proposed in order to assess easily, cost-effectively, and accurately the classification of defective insulators. Other algorithms such as support vector machine (SVM) and K-nearest neighbors (KNN) are used to validate the outcomes of the ANN proposed technique.

The common defects that could occur in the ceramic outdoor insulators are the breaking and cracking of the ceramic shell dielectric material. The occurrence of these defects depends on several factors, such as the places of these insulators, contamination degree, environmental conditions, and operating stresses.

Three samples of pin-cap ceramic insulators were tested in this work. Figure 2a shows the construction of the used insulator in this study that was acquired from the Egyptian Company for Manufacturing Electrical Insulators (ECMEI), Elsewedy Electric, with features43: 11 kV rating voltage, 255 mm diameter (D), 146 mm spacing (H), 320 mm creepage distance, and 90 kN mechanical strength. Variable artificial defects were introduced in two of them. One sample was completely broken and the other was cracked. The third one is considered the reference healthy sample without any apparent defects. Figure 2b shows the three samples tested in this study.

(a) Pin-cap insulator construction, and (b) Three samples of ceramic insulators: completely-broken insulator, cracked insulator, and healthy one.

This passage describes the experimental test setup used in this current study. The setup is shown in Fig. 3 and involves a 100 kV high voltage transformer that applies a test voltage to the samples being evaluated. The samples are tested vertically as normal operation, with the pin side connected to the high voltage terminal of the test transformer and the cap side grounded. To generate PD activities, the individual disc samples are exposed to an AC voltage of 40 kV, 50 Hz (sinusoidal waveform), in an air-insulated medium, which causes PD activities due to various defects. An 80 MHz acoustic sensor is used to capture the signals that the defective insulators emit. These signals are then transmitted via a BNC coaxial cable to a digital oscilloscope with a 500 MHz bandwidth and a 500 MS/s sampling rate for further analysis. The oscilloscope is linked to a personal computer (PC) through a GPIB cable for recording the radiated signals. 100 PD pulses are captured and recorded for each tested insulator, with each pulse comprising 4000 raw data points indicating the amplitude in mV versus time in µs.

After collecting acoustic emission signals from various partial discharge (PD) activities, the next step involves analyzing these signals to establish the connection between the acquired signal and the corresponding defect. As a result, a series of procedures are applied to the collected signals in order to extract and get useful information. In this study, the acoustic-collected signals are processed in four steps: wavelet transform, feature extraction, feature selection, and classification. Furthermore, the Fourier transform technique is also used to be compared to the wavelet transform analysis tool.

Discrete wavelet transform (DWT) is used as a first stage to decompose the original signal into two groups: approximations, which reflect the signal's high-scale and include low-frequency components, and details, which indicate the signal's low-scale and include high-frequency components. DWT is mainly used as a feature extraction technique for extracting characteristics or features from the decomposed high and low-frequency signals.

Mother wavelet is selected based on the similarity between AE signal and mother wavelet based on qualitative approaches. Normally, shape matching by visual inspection is applied to pick up the most proper mother wavelet. Several researchers worked on this point of selection of mother wavelet in case of power system transients such as acoustic emissions44,45,46,47,48,49. W. N. A. W. Mohammad et al.47 concluded that the forms of wavelets db, coif, sym, bior, and rbio are used since they are the most appropriate wavelets in the case of acoustic and electrical emission of PD signals. Safavian et al.48 concluded that the db4, coiflet, and b-spline were equally suitable in detecting power system transients. Accordingly, these findings are supposed to be a guide for this current work.

After decomposing the original signal by DWT into 5-levels of approximation and detail signals, the features can then be extracted from each decomposed level. Each of the wavelet components that have been decomposed yields seven descriptive waveform features: mean, variance, maximum amplitude, minimum amplitude, mean of energy, skewness, and kurtosis, which are characterized as follows:

Mean (m) is defined as the average value of the number of samples (n).

where: n is samples’ number and \({\text{x}}\) is the sequence of the samples.

Variance (V) is a statistical measure that quantifies the amount of variability or spread in a set of data values. It is calculated by taking the average of the squared differences of each data point from the mean.

Maximum amplitude of a signal refers to the highest value of the amplitude that the signal reaches during its cycle.

Minimum amplitude of a signal refers to the lowest value of the amplitude that the signal reaches during its cycle.

Mean of energy (me) is the energy mean value1 and can be calculated by taking the sum of the squares of the values in the signal, divided by the total number of values.

Skewness (S) is a measure of the extent of asymmetry in a distribution with reference to the sample mean1.

where: \(\upsigma\) is the standard deviation.

Kurtosis (K) is a measure of how peaked or flat a distribution is compared to a normal distribution1.

Following the extraction of the above seven features, the ANOVA test (the analysis of variance) was utilized as a feature selection technique to identify significant features at each level for the purpose of detecting different types of defects. Specifically, a one-way ANOVA test was employed to measure the statistical significance of differences between the means of three distinct groups: a healthy sample and two different types of defects. The variance ratio of mean squares between and within groups is the ANOVA F-distribution test statistic. The decision rule for this test is based on P-value. If the estimated P-value is more than a value of 0.05, at α-level = 0.05 with a 95% confidence level, significant differences exist between the tested groups.

The last stage of data processing is the pattern recognition or classification process, which identifies the types of PD activities. The present study utilizes an artificial neural network (ANN), commonly referred to as a neural network (NN), as an advanced classification tool for identifying various types of defective insulators. Generally, pattern recognition or classification algorithms include two stages: training, which is known as learning, and testing which is known as classification50. The role in the training stage is to model a mathematical relationship between the data sets and their respective PD pulses50. While in the testing phase, new input data points that were not part of the training data are defined as a single category of PD sources50. ANNs are a type of computational model that takes inspiration from the way biological neural networks in the human brain process input data. Figure 4 displays the structure of an ANN which comprises of three layers: an input layer, one or more hidden layers, and an output layer. In ANNs, a sequence of interconnected units or nodes are used, which are commonly referred to as artificial neurons. Each interlink, like the neurons in a living brain, has the capacity to transmit data or signals to other connections. These connections and neurons typically have a weight that varies as learning progresses. The weight can increase or decrease the signal intensity at a connection link. To get the neuron output, first the weighted sum of all points is taken, then a bias term is added to this sum50. Such a weighted sum, which is usually called the activation, is then passed via an activation function that generates the output results50.

This article does not contain any studies with human participants or animals performed by any of the authors.

In a laboratory environment, three samples were tested at 40 kV with a sinusoidal waveform at 50 Hz. Two of the samples were defective insulators, while the other one was healthy. Using a 500 MHz oscilloscope, the shape of the discharge pulse for each test sample was captured based on the amplitude of the discharge pulse in mV vs. time or samples. This is referred to as the time-domain characteristics of acoustic signals obtained from PD activities. Using the established data acquisition system (DAS), 100 discharge sound pulses were randomly obtained and recorded for each test sample.

The recorded acoustic emission signals are subjected to a Fast Fourier Transform (FFT) tool, which converts them into their frequency domain. This process enables the frequency bands for each test sample to be shown.

Figures 5, 6 and 7 display one of the collected waves for each of the three test samples in both domains: time and frequency. Visual inspection of the figures reveals differences in waveform shapes between the three test samples. Additionally, the magnitude of the PD sound pulse of the defective samples is higher than that of the healthy sample.

Single PD acoustic signal for a healthy insulator in time and frequency domains.

Single PD acoustic signal for a completely broken insulator disc in time and frequency domains.

Single PD acoustic signal for a cracked insulator disc in time and frequency domains.

Figure 8 shows PD signatures of all samples in the frequency domain. It has been observed from this figure that peaks of the spectrum amplitude have occurred at variable frequencies for each sample. That means there are significant differences between the tested samples.

Single PD acoustic signals for all tested samples in frequency domain.

Following recording, the PD acoustic emission signals gathered by the established DAS were transferred into the MATLAB software package and subjected to wavelet analyzer analysis.

For the selection of the mother wavelet, we visually examined the obtained signal for a best match with the available standard mother wavelets. By this visual inspection, it is found that the ‘‘db4″ mother wavelet is potentially most similar to the measured AE signatures shown in Figs. 5, 6 and 7. This observation is highly consistent with the outcomes of references44,47,48, and49.

Each captured signal is decomposed into 5-levels of approximations, which contain low frequency components, and other 5-levels of details, which contain high frequency components using the “db4” as a mother wavelet. This process is very difficult to be done manually for each signal of 100 PD pulses and repeated for all cases. So, a MATLAB code for DWT was designed to be used at any time for all sample cases. Figures 9 and 10 show the wavelet transform decomposition, in a MATLAB environment, of one PD acoustic wave captured with a broken insulator in separate and tree decomposition modes, respectively. Finally, each PD test signal in the wavelet analyzer is decomposed into five distinct decomposition signals using the below equation:

where: S is the main signal, a5 is the 5th level in approximation components, and d1, d2, d3, d4, d5 are the 5-levels in details respectively.

DWT separate mode decomposition for one PD pulse of broken disc.

Tree mode decomposition for one PD pulse of broken disc.

The seven features under investigation were cleverly extracted from the decomposed approximation and detail signals using the DWT m-file algorithm. For example, Table 1 provides the features that were extracted from the 6-decomposed components (a5, d1, d2, d3, d4, d5) of Fig. 6 in the time domain. These decomposed signals related to a single PD pulse collected from the broken insulator. This study focuses on the relative change in the estimated feature values as an indicator of the type of defect present rather than on the absolute values of these features. Likewise, an algorithm has been devised to extract and compute the features of the decomposed signals for the 100 PD signal waves acquired from each of the three samples studied in this work.

ANOVA analysis test is included in the m-file MATLAB code for minimizing the extracted features/levels and selecting the significant features/levels from the seven original features. Table 2 shows the estimated P-value for each feature/level. Each calculated P-value in that table shall be compared to 0.05, and the decision rule here is that if the computed P-values are less than 0.05, the corresponding features/levels are considered significant and could be ignored otherwise. The lowest two values are chosen for each corresponding feature. Consequently, two levels are selected from each extracted feature to be the most significant. Finally, 14-levels/features, as shown in Table 3, are selected and ready to be used as input data to the neural network for identification of the type of defects in the insulators.

The outcomes of the ANOVA test are highly consistent with the findings obtained through the F-value, J-value and B-value criteria, which were discussed in1,51, and52, respectively.

According to feature selection analysis, two levels were selected for each feature of the extracted seven features to be input data to the classifier, which is known as ANN as shown in Table 3. So, the input data is a matrix of 14 × 300 representing 300 samples of 14 elements, and the target (output) data is proposed to be 3 × 300 matrix representing 300 samples of 3 elements, as shown in Fig. 11. In this classifier, the 300 samples are randomly divided into 70% (210 samples) for training, 15% (45 samples) for the validation and 15% (45 samples) for testing. It has been observed from the results that the best performance of validation process is achieved at error 0.0816. This error is calculated as the deviation between the target (the proposed output of the ANN) and the actual output of the ANN itself. Further, the obtained overall recognition rate of these data is 68.119%. This obtained result is considered poor in the classification process indicating low accuracy of the designed classifier. In order to overcome this problem, authors have decided to increase the dataset for the ANN by collecting more acoustic emission signals to improve the performance of the classifier. So, the experimental process was repeated to obtain 200 acoustic signals for each test sample and data processing techniques were performed on 200 signals for each sample instead of 100 signals.

Now, the input data becomes a matrix of 14 × 600 and the target data is proposed to be a matrix of 3 × 600. Figure 12 shows that the best validation performance is obtained at 0.000765 mean squared error (MSE). This small error indicates the high performance of the developed classifier. Figure 13 shows a regression plot of training, validation, testing and the overall recognition rate of the data. It has been seen that the overall recognition rate of the classifier is 96.034% indicating a high accuracy and performance of the classifier.

Performance plot of ANN for DWT.

Regression plot of ANN for DWT.

On the other hand, from FFT analysis, the first ten peak values of each pulse are assumed to be input data to the ANN. So, the input data is a matrix of 10 × 600 and the output data is proposed to be the same as the previous classifier’s 3 × 600 matrix, as shown in Fig. 14. With this tool, the best validation performance is achieved at error 0.031838. In addition to that, the overall accuracy recognition rate is obtained at 88.647% as illustrated in Fig. 15.

Regression plot of ANN for FFT.

In conclusion, it has been observed, as cleared in Table 4, that the recognition rate obtained from DWT is higher than that obtained from FFT analysis. Additionally, the best validation performance is achieved with a lower error in the wavelet transform than in the FFT. Consequently, DWT analysis is more accurate and is recommended for use in classifying defects in ceramic outdoor insulators.

It is important to validate the findings of the Artificial Neural Network (ANN) to provide an alternative perspective on the classification performance and help assess the robustness of the ANN results. In this context, support vector machine (SVM) and K-nearest neighbors (KNN) are both employed to validate the findings obtained from ANN. SVM is a supervised learning algorithm that aims to find an optimal hyperplane to classify data points into different classes. KNN, on the other hand, is a non-parametric algorithm that classifies data points based on their proximity to the nearest neighbors in the training set.

SVM and KNN models are implemented using classification learner application in a MATLAB environment. The input dataset, obtained from the feature selection stage, was prepared and imported for training. Based on the results, the average value of SVM accuracy is 94.8% and KNN accuracy is 90.0%. These results can be observed from the confusion matrix for each model, as shown in Fig. 16. It has been observed that the achieved classification accuracy is high, reaching or exceeding 90.0%. Furthermore, it has been noted that the classification accuracies of these models are relatively close to each other, indicating a degree of consistency in their predictions. Therefore, the outcomes of the used validation algorithms increase confidence in the accuracy, stability, and reliability of the results.

Confusion matrix of SVM and KNN models.

The current research discusses an online safety monitoring technique for ceramic outdoor insulators with actual defects that could happen during service with high-bandwidth equipment.

In data processing techniques, the ANOVA test was introduced as an advanced tool for feature selection process, and its findings were matched with those of other tools used before.

It has been observed from ANN results that the overall recognition rate depends on the number of collected signals. It implies that a greater number of signals captured results in a higher recognition rate.

SVM and KNN algorithms were used to validate the outcomes of the proposed ANN technique. It has been found from the results that the ANN, SVM, and KNN models have matched with each other and are suitable tools for the classification of defects in high voltage outdoor ceramic insulators.

Detection and monitoring of PD is a significant diagnosis of defects in outdoor ceramic insulators for ensuring reliability and preventing any interruption in the electrical power network. As a result, variable defects in ceramic insulators have been studied in this current paper, which are known to be sources of PD activities. A DAS has been established for capturing and recording the acoustic emission signals resulting from PD activities in defective ceramic insulators. DWT has been introduced for extracting features from the captured signals and decomposing the original signals into multi-level signals to get more information about the acoustic signatures for each test sample. The ANOVA test has been adopted and used as a feature selection tool. Two levels for each extracted feature have been selected to be the most significant signatures for the classification of defective insulators and are ready to be the input dataset to the neural network, which is known as a classifier. ANN is used in this current work for classifying defects in ceramic insulators. It has been observed from ANN results that the overall recognition rate depends on the number of collected signals. It implies that a greater number of signals captured results in a higher recognition rate. The overall recognition rate is obtained at 96.03% from DWT and 88.65% from FFT, indicating a high accuracy and performance classifier. SVM and KNN models are used to validate the findings of the ANN technique. It has been observed that the classification accuracy of these models is relatively close to each other, indicating a degree of consistency in their predictions. Therefore, the outcomes of the used validation algorithms increase confidence in the accuracy, stability, and reliability of the results. It is concluded that a successful neural network analysis for the classification of defected ceramic insulators could have important practical applications for the safety and reliability of the electrical power transmission and distribution system.

The data sets used and/or analyzed during the current study are available from the corresponding author on reasonable request.

Ahmed S. Haiba, Gad, A., El-Debeikey, S. M. & Halawa, M. M. Statistical Significance of Wavelet Extracted Features in the Condition Monitor- ing of Ceramic Outdoor Insulators. in IEEE Electrical Insulation Conference (EIC) 335–432 (2019). https://doi.org/10.1109/EIC43217.2019.9046590.

Anjum, S. A Study of the Detection of Defects in Ceramic Insulators Based on Radio Frequency. (University of Waterloo, 2014).

Cherney, E. A. & Hooton, R. D. Cement growth failure mechanism in porcelain suspension insulators. IEEE Trans. Power Deliv. https://doi.org/10.1109/MPER.1987.5527324 (1987).

Cherney, E. A. Electromechanical integrity of suspension insulators. Res. Rev. - Ontario Hydro 19–23 (1982).

Zhao, C. et al. Development of contamination flashover pre-warning system and analysis of operating experience. IEEE Trans. Dielectr. Electr. Insul. 22, (2015).

Zhang, Z., Liu, X., Jiang, X., Hu, J. & Gao, D. W. Study on AC flashover performance for different types of porcelain and glass insulators with non-uniform pollution. IEEE Trans. Power Deliv. 28, 1691–1698 (2013).

Article  ADS  CAS  Google Scholar 

Chrzan, K. L. Leakage currents on naturally contaminated porcelain and silicone insulators. IEEE Trans. Power Deliv. 25, 904–910 (2010).

Chrzan, K. L., Vosloo, W. L. & Holtzhausen, J. P. Leakage current on porcelain and silicone insulators under sea or light industrial pollution. IEEE Trans. Power Deliv. 26, (2011).

He, L. & Gorur, R. S. Source strength impact analysis on insulator flashover under contaminated conditions. IEEE Trans. Dielectr. Electr. Insul. 23, 1005–1011 (2016).

Zener, C. & Wills, H. H. A theory of the electrical breakdown of solid dielectrics. Z. Phys. 145, 523–529 (1934).

Polisetty, S. K. Partial discharge classification using acoustic signals and artificial neural networks and its application in detection of defects in Ceramic insulators. (University of Waterloo, 2019).

Ghosh, R., Chatterjee, B. & Dalai, S. A method for the localization of partial discharge sources using partial discharge pulse information from acoustic emissions. IEEE Trans. Dielectr. Electr. Insul. 24, 237–245 (2017).

IEC Standards 60270. High-voltage test techniques. Partial discharge measurements (IEC 60270:2000). Bsi (2000).

Albano, M., Waters, R. T., Charalampidis, P., Griffiths, H. & Haddad, A. Infrared analysis of dry-band flashover of silicone rubber insulators. IEEE Trans. Dielectr. Electr. Insul. 23, 304–310 (2016).

FRĄCZ, P. Comparison of two methods for detection of UV signals emitted by PD on HV insulators made of porcelain. Przegląd Elektrotechniczny 1, 104–106 (2016).

Si, W. R., Li, J. H., Li, D. J., Yang, J. G. & Li, Y. M. Investigation of a comprehensive identification method used in acoustic detection system for GIS. IEEE Trans. Dielectr. Electr. Insul. 17, (2010).

Yaacob, M. M., Alsaedi, M. A., Rashed, J. R., Dakhil, A. M. & Atyah, S. F. Review on partial discharge detection techniques related to high voltage power equipment using different sensors. Photonic Sensors vol. 4 325–337 at https://doi.org/10.1007/s13320-014-0146-7 (2014).

Sahoo, N. C., Salama, M. M. A. & Bartnikas, R. Trends in partial discharge pattern classification: A survey. IEEE Trans. Dielectr. Electr. Insul. 12, (2005).

Ilkhechi, H. D. & Samimi, M. H. Applications of the Acoustic Method in Partial Discharge Measurement: A Review. IEEE Trans. Dielectr. Electr. Insul. 28, (2021).

Hussain, M. R., Refaat, S. S. & Abu-Rub, H. Overview and partial discharge analysis of power transformers: a literature review. IEEE Access 9, 64587–64605 (2021).

Mantach, S. et al. Deep learning in high voltage engineering: a literature review. Energies 15. https://doi.org/10.3390/en15145005 (2022).

Stefenon, S. F. et al. Classification of insulators using neural network based on computer vision. IET Gener. Transm. Distrib. 16, (2022).

Sampedro , C. , Rodriguez-Vazquez , J. , Rodriguez-Ramos , A. , Carrio , A. & Campoy , P. Deep learning-based system for automatic recognition and diagnosis of electrical insulator strings .IEEE Access 7, (2019).

Shi, C. & Huang, Y. Cap-count guided weakly supervised insulator cap missing detection in aerial images. IEEE Sens. J. 21, (2021).

Arzamasov, V., Bohm, K. & Jochem, P. Towards Concise Models of Grid Stability. in 2018 IEEE International Conference on Communications, Control, and Computing Technologies for Smart Grids, SmartGridComm 2018 (2018). https://doi.org/10.1109/SmartGridComm.2018.8587498.

Aghamohammadi, M. R. & Abedi, M. DT based intelligent predictor for out of step condition of generator by using PMU data. Int. J. Electr. Power Energy Syst. 99, 95–106 (2018).

Gupta, A., Gurrala, G. & Sastry, P. S. An online power system stability monitoring system using convolutional neural networks. IEEE Trans. Power Syst. 34, (2019).

Zare, H., Alinejad-Beromi, Y. & Yaghobi, H. Intelligent prediction of out-of-step condition on synchronous generators because of transient instability crisis. Int. Trans. Electr. Energy Syst. 29, (2019).

Chen, M. et al. XGBoost-based algorithm interpretation and application on post-fault transient stability status prediction of power system. IEEE Access 7, (2019).

Dadashizadeh Samakosh, J. & Mirzaie, M. Flash-over voltage prediction of silicone rubber insulators under longitudinal and fan-shaped non-uniform pollution conditions. Comput. Electr. Eng. 78, 50–62 (2019).

Belhouchet, K., Bayadi, A. & Bendib, M. E. Artificial neural networks and genetic algorithm modelling and identification of arc parameter in insulators flashover voltage and leakage current. Int. J. Comput. Aided Eng. Technol. 11, 1–13 (2019).

Salem, A. A. et al. Artificial intelligence techniques for predicting the flashover voltage on polluted cup-pin insulators. in Advances in Intelligent Systems and Computing 1073, 362–372 (Springer, 2020).

Mahdjoubi, A., Zegnini, B., Belkheiri, M. & Seghier, T. Fixed least squares support vector machines for flashover modelling of outdoor insulators. Electr. Power Syst. Res. 173, 29–37 (2019).

Asimakopoulou, G. E. et al. A fuzzy logic optimization methodology for the estimation of the critical flashover voltage on insulators. Electr. Power Syst. Res. 81, 580–588 (2011).

Farshad, M. Detection and classification of internal faults in bipolar HVDC transmission lines based on K-means data description method. Int. J. Electr. Power Energy Syst. 104, 615–625 (2019).

Lu, S. et al. A weekly load data mining approach based on hidden markov model. IEEE Access 7, 34609–34619 (2019).

Salem, A., Abd-Rahman, R., Ghanem, W., Al-Gailani, S. & Al-Ameri, S. Prediction flashover voltage on polluted porcelain insulator using ANN. Comput. Mater. Contin. 68, 3755–3771 (2021).

Tahir Khan Niazi, M. et al. Prediction of critical flashover voltage of high voltage insulators leveraging bootstrap neural network. Electron. 9, (2020).

Surya Prasad, P. & Prabhakara Rao, B. Review on machine vision based insulator inspection systems for power distribution system. J. Eng. Sci. Technol. Rev. 9, (2016).

Salem, A. A. A. et al. An alternative approaches to predict flashover voltage on polluted outdoor insulators using artificial intelligence techniques. Bull. Electr. Eng. Informatics 9, (2020).

Din, A., Piah, M. A. M., Abdullah, A. R. & Abdullah, F. S. Classification of degraded polymer insulator using support vector machine. in Proceedings of the IEEE International Conference on Properties and Applications of Dielectric Materials vols 2021-July (2021).

Saranya, K. & Muniraj, C. A SVM based condition monitoring of transmission line insulators using PMU for smart grid environment. J. Power Energy Eng. 04, (2016).

https://www.elsewedyelectric.com/en/business-lines/wire-cable-accessories/insulators/.

Ngui, W. K., Leong, M. S., Hee, L. M. & Abdelrhman, A. M. Wavelet analysis: Mother wavelet selection methods. in Applied Mechanics and Materials vol. 393 (2013).

Ahadi, M. & Bakhtiar, M. S. Leak detection in water-filled plastic pipes through the application of tuned wavelet transforms to Acoustic Emission signals. Appl. Acoust. 71, (2010).

Loutas, T. H., Sotiriades, G. & Kostopoulos, V. On the application of wavelet transform of AE signals from composite materials. Engineering (2004).

Mohammad, W. N. A. W. et al. Analysis on multiple acoustic and electrical emission of PD signal based on signal to noise ratio (SNR) on power cable. in Proceeding - 2020 IEEE 8th Conference on Systems, Process and Control, ICSPC 2020 (2020). https://doi.org/10.1109/ICSPC50992.2020.9305756.

Safavian, L. S., Kinsner, W. & Turanli, H. A quantitative comparison of different mother wavelets for characterizing transients in power systems. in Canadian Conference on Electrical and Computer Engineering vol. 2005 (2005).

Yang, L., Judd, M. D. & Bennoch, C. J. Denoising UHF signal for PD detection in transformers based on wavelet technique. in Annual Report - Conference on Electrical Insulation and Dielectric Phenomena, CEIDP (2004). https://doi.org/10.1109/ceidp.2004.1364215.

Ma, H., Chan, J., Saha, T. K. & Ekanayake, C. Pattern recognition techniques and their applications for automatic classification of artificial partial discharge sources. IEEE Trans. Dielectr. Electr. Insul. 20, (2013).

Sinaga, H. H., Phung, B. T. & Blackburn, T. R. Recognition of single and multiple partial discharge sources in transformers based on ultra-high frequency signals. IET Gener. Transm. Distrib. 8, (2014).

Anjum, S., Jayaram, S., El-Hag, A. & Jahromi, A. N. Detection and classification of defects in ceramic insulators using RF antenna. IEEE Trans. Dielectr. Electr. Insul. 24, (2017).

Open access funding provided by The Science, Technology & Innovation Funding Authority (STDF) in cooperation with The Egyptian Knowledge Bank (EKB).

Electrical Metrology Division, National Institute of Standards (NIS), Giza, Egypt

Ahmed S. Haiba & A. Eliwa Gad

You can also search for this author in PubMed  Google Scholar

You can also search for this author in PubMed  Google Scholar

Both authors contributed in this work. A.S.H. suggested the idea of the current work and implemented the experimental section and contributed in analysis of signal processing section. A.E.G. contributed in designing the ANN for both DWT and FFT. A.S.H. and A.E.G. implemented the validation of results. A.S.H. wrote the original draft preparation and A.E.G. shared completing the paper writing. Both A.S.H. and A.E.G. reviewed and edited the paper. The tables and figures were prepared by both A.S.H. and A.E.G. Both authors read and approved the final manuscript. The first author A.S.H. is the corresponding author.

Correspondence to Ahmed S. Haiba.

The authors declare no competing interests.

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Open Access This article is licensed under a Creative Commons Attribution 4.0 International License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons licence, and indicate if changes were made. The images or other third party material in this article are included in the article's Creative Commons licence, unless indicated otherwise in a credit line to the material. If material is not included in the article's Creative Commons licence and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder. To view a copy of this licence, visit http://creativecommons.org/licenses/by/4.0/.

Haiba, A.S., Eliwa Gad, A. Artificial neural network analysis for classification of defected high voltage ceramic insulators. Sci Rep 14, 1513 (2024). https://doi.org/10.1038/s41598-024-51860-8

DOI: https://doi.org/10.1038/s41598-024-51860-8

Anyone you share the following link with will be able to read this content:

Sorry, a shareable link is not currently available for this article.

Provided by the Springer Nature SharedIt content-sharing initiative

By submitting a comment you agree to abide by our Terms and Community Guidelines. If you find something abusive or that does not comply with our terms or guidelines please flag it as inappropriate.

Scientific Reports (Sci Rep) ISSN 2045-2322 (online)

Composite insulator Sign up for the Nature Briefing newsletter — what matters in science, free to your inbox daily.