Thank you for visiting nature.com. You are using a browser version with limited support for CSS. To obtain the best experience, we recommend you use a more up to date browser (or turn off compatibility mode in Internet Explorer). In the meantime, to ensure continued support, we are displaying the site without styles and JavaScript.

Scientific Reports volume  13, Article number: 20754 (2023 ) Cite this article ac motor soft starters

Numerous integrals of the fundamental frequency are known as harmonics and can be found in power systems or electrical circuitry systems. Non-linear loads occasionally drain current or contains a varying impedance with each period of the AC voltage are often responsible for power system harmonics. This can result in system overheating, system losses, and equipment or system damage. In order to achieve the IEEE 519 power quality standard, filters are routinely employed to lower harmonic levels. In this work, we designed a single tuned passive filter (STPF) to minimize harmonics of sequence 5th, 7th, 11th, 13th, 17th, and 19th in a three (3) phase power system. The measurements were taken at the point of common coupling. To test the filter performance, the system and STPF were designed in MATLAB/Simulink, and the simulated results produced without and with STPF were compared. The \({THD}_{I}\) was reduced from 14.93% down to 4.87% when STPF was connected which is within the IEEE 519-2022 standard; proving that the STPF was effective in decreasing the harmonics to the desired level.

When constructing both AC and DC distribution systems, power quality (PQ) is critical1. Control of power systems must be harmonious since PQ is a key study issue2. In IEEE 1100 standards, PQ is defined as the principle of powering and grounding sensitive electronic devices in a manner appropriate for the equipment3. PQ can also refer to the quality of power or voltage, which changes depending on the source and is merely the interface between the utility and the user. Although the voltage quality of a power system is commonly considered as the PQ, the voltage signal which is sinusoidal is reliant on the current signals, therefore analyzing the load’s current is critical. However, the electrical system's wires, cables, and other components experience voltage drops as a result of non-sinusoidal current flow, which distorts the sinusoidal voltage waveform4. Due to the widespread use of electronic devices, electric loads witnessed a tremendous change. These loads are the primary causes and victims of PQ problems, they disrupt the voltage waveform constituting a variety of disturbances5 due to their unpredictable nature6. When the loads change gradually, changes in the supply voltage can be easily controlled with voltage regulators. On the other side, when the loads impedance varies quickly, novel supply voltage occurrences, including sags, swells, notches, and flicker arise. The problem shifts from one of loading quality to one of supply quality7. Table 1 shows a few typical power quality issues and Fig. 1 shows some power quality issues and the need for a rectification technique.

PQ issues and rectification6 (Published under open access).

Numerous efforts have recently been carried out to improve the quality of components affected by harmonics in a variety of ways, including functionality and efficiency enhancement, harmonic suppression, and downsizing8.

This paper begins with an introductory section that outlines several PQ concerns. In “Harmonics” section, harmonics is the most serious PQ issue; passive filters as a mitigating model; related work on the use of passive filters for harmonics mitigation and their effectiveness in comparison with the IEEE 519 standard were discussed. STPF; its configuration, function, parameters, and mathematical model was captured in “Methodology” Section. In “Methodology” section also describes the approach, which includes a flowchart, measurements, and a mathematical model for computing various STPF parameters, as well as the MATLAB/Simulink simulation platform. The findings of the study were addressed in “Result and discussion” section, and lastly, a conclusion and recommendation are presented in “Conclusion” section.

Among the listed power quality issues, harmonics is the most concern. It is considered be the multiple integral of fundamental frequency9. As a result of a rise in non-linear loads, harmonic issues have recently become more important10,11. As a consequence of advancements in technology, including the usage of power electronic circuits, equipment for AC to DC transmission connections, loads for power electronics-based power system regulation, and microprocessor controllers12, and renewable energy applications13. A substantial quantity of harmonic distortion in the power systems is caused by the expanding use of distributed, renewable, intermittent power sources, the spread of power electronic equipment and nonlinear loads which have high levels of uncertainty14. The two main effects of PQ problems on the transmission network appears to be the possibility for equipment failure to negatively impact efficiency and the drop in power factor caused by specific forms of harmonics. Figure 2, demonstrates harmonic current flow through all the system's impedances towards the source from a non-linear load with a filter connected to turn the harmonic current away from the sources and toward ground.

Harmonic current flowing because of a non-linear load.

A key PQ issue in power systems, harmonic distortion, might lead to more breakdowns of equipment and communications interference15, fuse and breaker malfunction, transformer overheating, device malfunction16, conductor heating, power loss, decrease in power factor and financial losses17. To completely control harmonic interference, since it cannot be completely removed from the system because some of the harmonics are created by system equipment. Users' ability to generate a certain quantity of harmonic current is constrained by the IEEE 519 standard. Systems of rewards and penalties are applied to consumers according to the amount of harmonic current they emit. The technique is put into practice after each harmonic source has been fairly and openly evaluated. Table 2 displays a few system consequences of current and voltage distortion, while the main effects of harmonic current and voltage on the power system are shown in Table 3.

Passive filter can mitigate most of the PQ issues18. It has an advantage of low cost, simplicity, flexibility19 and comes in variety of configurations20 with various frequency response properties21. One of the efficient methods used to stop or slow the spread of harmonics in the electrical grid is the use of passive harmonic filters. Compared to active filters, passive filters are more stable, capable of withstanding huge currents, and substantially less expensive22. The STPFs, double tuned passive filters, damped filters (high and band-pass, second-order, third-order), C-type passive filter, and composite passive filter11,23,24 are all types of passive filters. In literature, several studies on filter setup in dispersed networks have been conducted25.

In the study of Mambidala et al.10, a new three-phase single tuned harmonic filter was developed to improve the utility grid's voltage profile, current profile, and total harmonic distortion. \({THD}_{I}\) was measured from the current source obtaining 16.5% without filter and after the proposed new three-phase tuned harmonic filter was introduced the \({THD}_{I}\) reduced to 0.02% establishing the effectiveness of the filter in mitigating harmonics. Furthermore, it was observed that when three, two and one electric vehicle(s) (EV) batteries were connected, the \({THD}_{V}\) without filter was 11.82%, 20.60% and 28.87%, respectively, and after the filter was connected the \({THD}_{V}\) dropped to 0.18%, 0.0%, and 0.0% when three, two and one EV batteries were connected, respectively.

Melo et al.15, outlined an optimization issue for sizing and placing STPFs in power supply networks with the aim of reducing overall distortion from harmonics. The \({THD}_{V}\) before the utilization of filter were as follows: bus 63,\({THD}^{a}\left(\%\right)=6.060\) , \({THD}^{b}\left(\%\right)=5.3933\) , \({THD}^{c}\left(\%\right)=4.8699\) , after the filter was applied, 63, \({THD}^{a}\left(\%\right)=3.2062\) , \({THD}^{b}\left(\%\right)=4.1038\) , \({THD}^{c}\left(\%\right)=2.9476\) . This clearly shows that the single tuned passive filter was effective.

Similarly, in the study of Anuar and Abdullah16, at the point of common coupling (PCC), a passive power harmonic filter was used to remove notable current harmonics (5th, 7th, and 11th) from a 240 V (rms) utility. The \({THD}_{V}\) values for phase A, B, and C systems without filters are 24.36%, 29.19%, and 29.39%, respectively. When the filter was connected, \({THD}_{V}\) dropped to 7.83% in phase A, 10.78% in phase B, and 10.24% in phase C.

The study of18 presented a single phase shunt active filter supported by controllers. At steady state, the grid’s current \({THD}_{I}\) with the three controllers proportional integral to low pass filter (PI-LPF), PI-dual self-tuning filter (PI-DSTF) and back stepping controller-DSTF (BSC-DSTF) are observed at 7.5%, 4.2% and 4.2%, respectively. The grid current \({THD}_{I}\) is improved with the DSTF controller within the IEEE 519 standard.

Also, Bajaj and Singh23 employed the firefly algorithm (FA) to address the design of various passive power filter (PPF) types, which is formulated as an optimization problem with the goal of increasing the penetration of a renewable distribution system (DG) in a distorted distribution power grid. The filters were ranked from less effective to most effective as composites types in terms of their performance and the percentage of penetration level after simulation was carried out; single-tuned, second-order damped, C-type, and third-order damped. In time of high cost, the order reverses.

In the work of Khattab et al.11, a mathematical model of a novel fourth-order harmonic passive filter damped high pass filter (DHPF) is proposed alongside considering various design scenarios. The crow spiral based search algorithm (CSSA) is applied to solve the design issues. \({THD}_{I}\) and \({THD}_{V}\) without filter are 5.13% and 6.55% respectively. The second order filter was applied the \({THD}_{I}\) and \({THD}_{V}\) reduced to 4.36 and 3.16, respectively, third order filter produced \({THD}_{I}\) and \({THD}_{V}\) of 4.18 and 3.15, respectively. The C-type filter generated \({THD}_{I}\) and \({THD}_{V}\) of 4.47 and 3.10, respectively. The proposed DHPF obtained \({THD}_{I}\) and \({THD}_{V}\) value of 4.18% and 2.90, respectively, demonstrating the effective of the filter within the IEEE-519 standard.

Harmonic is a significant challenge to power systems that cannot be completely eliminated but can be mitigated. The reason for this is that some of the power equipment used for power system setup cause some losses themselves, and because the equipment comprises a significant portion of the system and is required for the power system to operate, the equipment cannot simply be removed from the system. The solution is to reduce the rate of losses caused by the equipment in the power system.

In this paper, we proposed STPF as a harmonic mitigation technique is employed after identifying harmonics as a key issue impacting PQ because of its advantages of low component cost, compact size, simplicity in design, affordable, and improves power quality. The novelty of our paper, which is presented in the design of STPF for a specific three phase plastic processing industry power system to mitigate harmonics of the following sequence 5th, 7th, 11th, 13th, 17th, and 19th adaptable for high frequency applications that is tested for effective harmonics mitigation in accordance with the IEEE 519-2022 standard (advanced of both IEEE 519-1992 and IEEE 519-2014)26.

A STPF is meant to filter out a single harmonic, and is straightforward to develop13 inexpensively with components that are all connected in series: a resistor (R), an inductor (L), and a capacitor (C)27, which provides low impedance path28. It enables harmonic current to flow across and reach the ground as shown in Fig. 2. In this study, STPF was used as a corrective measure to reduce the harmonics in the power system. Figure 3 shows the configuration of STPF.

In STPF design, the following essential parameter were considered R, C, L, \(X_{c}\) and \(Q_{c}\) . Where \(X_{c}\) denotes capacitance reactance,\(Q_{c}\) reactive power to improve power factor (Q) and prevent the electric power provider from imposing any fines. In most cases, Q adjustment is performed to raise the Q to around 0.98 or above.

where power factor \((p_{f} )\) , capacitance reactive power \((Q_{c}\) ), capacitance \(\left( C \right)\) , active power \(\left( P \right)\)

STPF has a predisposition to engage with the system, testing every imaginable interaction with the system is especially useful. For safety reasons, STPF is tuned slightly below the harmonic frequency. In the presence of mutual inductances, the tuning of the STPF to eliminate specific harmonics is not done adequately, and the filter's efficiency is diminished in practice29.

The following are the processes required to implement the proposed method as demonstrated in the flow chart in Fig. 4:

Measurement from PCC is obtained.

STPF parameters R, L, and C are calculated.

The power system is designed using MATLAB/Simulink.

Measure \({THD}_{I}\) without STPF in the system.

Design STPF, connect to the 3-phase power system and measure \({THD}_{I}\) .

Compare \({THD}_{I}\) without and with STPF.

Compare \({THD}_{I}\) with STPF and IEEE 519-2022

STPF is effective if \({THD}_{I}\) with STPF is equal to or less than IEEE 519-2022 standard.

The effectiveness of STPF is determined.

A flow chart demonstrating the methodology flow.

Metrel MI 2392 Power Q Plus Power Quality Analyzer was used to measure current, voltage, active power, reactive power, apparent power and harmonics at PCC30, the following results were obtained as shown in Table 4 from a balanced three phase load and analysis was carried out considering one phase. The \({THD}_{I}\) content in plastic processing industry load is 14.93%, as shown in Table 4 which exceeds the IEEE 519-2022 limit of less than 5%. This paper proposes a STPF that will reduce the \({THD}_{I}\) to the IEEE 519-2022 benchmark. The estimations for the RLC component are presented in Table 5.

Supposedly, \({P}_{f}\) changes from \({p}_{f1}\) = 0.94 to \({p}_{f2}\) = 0.99. These numbers are used to calculate the capacitor capacity (\({Q}_{c}\) ).

\(X_{C} = \frac{{V_{C}^{2} }}{{Q_{C} }}\)  = \(\frac{{234.45^{2}_{c} }}{17750.66}\)  = 3.09661 Ω, using (1).

\(X_{L} = X_{C}\)  = 3.09661 Ω at resonance.

Figure 5a without connecting STPF shows the distorted current waveform with ripple at it top nearly square appearance not quite sinusoidal, due to harmonics was obtained by MATLAB/Simulink simulation model. Figure 5b demonstrates the sequence of the harmonics having a primary frequency of 50 Hz and \({THD}_{I}\) value of 15.63% which is above the IEEE 519-2022 rate, showing the requirement for a filter to minimize the \({THD}_{I}\) to the accepted level. Harmonics of sequence 5th, 7th, 11th, 13th, 17th, and 19th stood out amongst others as shown in Fig. 5b.

(a) Current signal aberration, (b) \({THD}_{I}\) preceding system's application of the filter.

The simulation outcome when STPF was employed demonstrate the improvement of the magnitude of the current waveform as shown in Fig. 6a and the decrease in \({THD}_{I}\) from 15.63 to 4.87% as illustrated in Fig. 6b, accordingly. The \({THD}_{I}\) outcome from the simulation conforms to the IEEE 519-2022 standard.

(a) Waveform of the current after applying STPF, (b) \({THD}_{I}\) after STPF was used to reduce 5th, 7th, 11th, 13th, 17th, and 19th sequence.

Figure 7a shows the deformed current waveform with ripples at its top, while Fig. 7b shows the nearly perfect sinusoidal waveform that resulted from the STPF's influence.

(a) Current distortion due to non-linear load, (b) STPF filter effect of current signal.

Table 6 compares the distinct harmonics of particular order considering measurements before and after connecting the STPF as well as STPF and the IEEE 519-2022 standard. Table 6's outcome in column four demonstrates that both the individual and \(({THD}_{I}\) ) were in compliance with the standards following the application of STPF.

Figure 8a and b provide a plot of the results of Table 6, highlighting the diversity in each of the unique harmonic orders. Figure 8a shows the entire harmonics including the fundamental harmonic while in Fig. 8b, sequence 5th, 7th, 9th, 11th, 13th, and 19th without the 1st order harmonic were captured. The bar in blue color denotes the measured value at the PCC, the red colored bar denotes the individual harmonic without STPF (WOSTPF) connected, the ash-colored bar denotes the individual harmonic with STPF (WSTPF) connected, and the yellow-colored bar represents the IEEE 519-2022 standard.

A bar chart of the results obtained at PCC for WOSTPF, WSTPF, and IEEE 519-2022 sequences (a) 1st, 5th, 7th, 11th, 13th, 17th, and 19th, (b) 5th, 7th, 11th, 13th, 17th, and 19th.

The power system’s \({THD}_{I}\) value obtained was 15.63% without STPF connected to the 3-phase power system, with the connection of STPF the value was reduced from 15.63 to 4.87% within the IEEE 519-2022 standard which shows the effectiveness of the STPF filter used in minimizing harmonics in the power system. The STPF was successfully tuned to mitigate harmonics of sequence 5th, 7th, 11th, 13th, 17th, and 19th. Difficulties encountered when designing the system are particularly connected to the individual and overall harmonic distortion limits for both current and voltage at the PCC. STPF was only able to eliminate harmonics one at a time and was developed with a fixed nonlinear load, despite the fact that the load frequency can rapidly change.

STPF is unable to deal with frequency variations in the load, fails to eliminate frequencies other than the adjusted ones, and has issues with series/parallel resonance resulting to the need of more filters. To produce a superior overall result, a double tuned passive filter, damped filters or hybrid harmonic filter combination of an active–passive filter may be required. The optimization technique can be used to find the optimal STPF sizing by taking into consideration the total filter size due to changes in THD and determining the best R, L, and C for the filter.

All data generated or analyzed during this study are included in this published article.

Iacobici-Luca, N., Frigura-Iliasa, F. M., Vatau, D. & Andea, P. Power quality assessment system for a 220 kV/110 kV high voltage power station. In 2016 Electric Power Quality and Supply Reliability (PQ) 267–272 (IEEE, 2016).

Pasaribu, F. I., Sara, I. D., Tarmizi, T. & Nasaruddin, N. Harmonics step filter control model in household electricity. In 2023 2nd International Conference on Computer System, Information Technology, and Electrical Engineering (COSITE) 165–170 (IEEE, 2023).

Alves, M. F. & Ribeiro, T. N. Voltage sag: An overview of IEC and IEEE standards and application criteria. In 1999 IEEE Transmission and Distribution Conference (Cat. No. 99CH36333), vol. 2, 585–589 (IEEE, 1999).

Biryulin, V. I., Gorlov, A. N. & Kudelina, D. V. Modeling cable lines heating by currents of higher harmonics and interharmonics. In 2019 International Conference on Industrial Engineering, Applications and Manufacturing (ICIEAM) 1–5 (IEEE, 2019).

Yadav, A., Yadav, D., Kishore, K., Varshney, L. & Alam, M. S. Dynamic voltage restorer along with active and passive filter for power quality improvement in distribution network. In 2021 International Conference on Advance Computing and Innovative Technologies in Engineering (ICACITE) 714–717 (IEEE, 2021).

De Almeida, A., Moreira, L. & Delgado, J. Power quality problems and new solutions. In International Conference on Renewable Energies and Power Quality, vol. 3, 1–45 (2003).

Ferrero, A. Measuring electric power quality: Problems and perspectives. Measurement 41, 121–129 (2008).

Jamshidi, M., Siahkamari, H., Roshani, S. & Roshani, S. A compact Gysel power divider design using U-shaped and T-shaped resonators with harmonics suppression. Electromagnetics 39, 491–504 (2019).

Arif, M. R., Mahmood, F., Hashmi, M. & Hänninen, S. Application of passive filters to mitigate power quality problems caused by induction furnaces. in 2012 IEEE International Conference on Condition Monitoring and Diagnosis 1227–1230 (IEEE, 2012).

Mamidala, S., Prajapati, A. K. & Ravada, S. Modeling of buck converter charging station to improve the power quality using three phase single tuned harmonic filter for electric transportation. In 2022 IEEE 2nd International Conference on Sustainable Energy and Future Electric Transportation (SeFeT) 1–6 (IEEE, 2022).

Khattab, N. M. et al. A novel design of fourth-order harmonic passive filters for total demand distortion minimization using crow spiral-based search algorithm. Ain Shams Eng. J. 13, 101632 (2022).

Jaisiva, S., Neelan, S. & Ilansezhian, T. Harmonic analysis in non-linear loads of power system. Int. Res. J. Eng. Technol. 3, 1474–1478 (2016).

Zobaa, A. M., Abdel Aleem, S. H. E. & Youssef, H. K. M. Bi-level damped double-tuned harmonic passive filters design: Multi-criteria decision-making analysis. Ain Shams Eng. J. https://doi.org/10.1016/j.asej.2022.102082 (2022).

Santos, E., Khosravy, M., Lima, M. A., Cerqueira, A. S. & Duque, C. A. ESPRIT associated with filter bank for power-line harmonics, sub-harmonics and inter-harmonics parameters estimation. Int. J. Electr. Power Energy Syst. 118, 105731 (2020).

Melo, I. D., Pereira, J. L., Variz, A. M. & Ribeiro, P. F. Allocation and sizing of single tuned passive filters in three-phase distribution systems for power quality improvement. Electr. Power Syst. Res. 180, 106128 (2020).

Anuar, M. N. K. & Abdullah, N. Dominant harmonic current reduction using passive power filter. In 2022 IEEE International Conference on Power and Energy (PECon) 186–191 (IEEE, 2022).

Shakeri, S., Esmaeili, S. & Koochi, M. H. R. Passive harmonic filter design considering voltage sag performance-applicable to large industries. IEEE Trans. Power Deliv. 37, 1714–1722 (2021).

Jayasankar, V. N. & Vinatha, U. Backstepping controller with dual self-tuning filter for single-phase shunt active power filters under distorted grid voltage condition. IEEE Trans. Ind. Appl. 56, 7176–7184 (2020).

Zobaa, A. F. & Aleem, S. H. E. A. A new approach for harmonic distortion minimization in power systems supplying nonlinear loads. IEEE Trans. Ind. Inform. 10, 1401–1412 (2014).

Gumilar, L., Cahyani, D. E., Afandi, A. N., Monika, D. & Rumokoy, S. N. Optimalization harmonic shunt passive filter using detuned reactor and capacitor bank to improvement power quality in hybrid power plant. In AIP Conference Proceedings, vol. 2217 (AIP Publishing, 2020).

Singh, G. K. Power system harmonics research: A survey. Eur. Trans. Electr. Power 19, 151–172 (2009).

Boharb, A., El Markhi, H., El Moussaoui, H. & Lamhamdi, T. Profitability of filtering harmonics by passive filters for tertiary buildings: Application to a university of higher education. Electr. Eng. https://doi.org/10.1007/s00202-023-01970-9 (2023).

Bajaj, M. & Singh, A. K. Increasing renewable energy penetration in harmonically polluted distribution grids using passive filtering: A comparative assessment of common filter types. Electr. Eng. 104, 2979–3005 (2022).

Abood, S. B. & Abdul-Wahhab, T. M. Investigation of harmonic reduction using passive filters in a distribution network in Basra City. In IOP Conference Series: Materials Science and Engineering, vol. 1067, 012124 (IOP Publishing, 2021).

Xu, Y., Tang, Y. & Hong, W. Optimal configuration of filters for harmonic suppression in microgrid. In 2014 16th International Conference on Harmonics and Quality of Power (ICHQP) 561–565 (IEEE, 2014).

Power quality—IEEE 519-2022. Comsys https://comsys.se/our-adf-technology/power-quality-ieee-519-2022/.

Cho, Y.-S. & Cha, H. Single-tuned passive harmonic filter design considering variances of tuning and quality factor. J. Int. Counc. Electr. Eng. 1, 7–13 (2011).

Bagheri, A. & Alizadeh, M. Designing a passive filter for reducing harmonic distortion in the hybrid micro-grid including wind turbine, solar cell and nonlinear load. Prz Elektrotech. 95, 9–12 (2019).

Rahat, O., Saniei, M. & Seifossadat, S. G. Modeling and new tuning of the distribution transformer-integrated passive power filter and its effects on the transformer performance and network power quality. Electr. Power Syst. Res. 214, 108844 (2023).

Popescu, M., Bitoleanu, A. & Suru, V. On the design of LCL filter with passive damping in three-phase shunt active power filters. In 2016 International Symposium on Power Electronics, Electrical Drives, Automation and Motion (SPEEDAM) 825–830 (IEEE, 2016).

Fahmi, M. I., Baafai, U., Hazmi, A. & Nasution, T. H. Harmonic reduction by using single-tuned passive filter in plastic processing industry. IOP Conf. Ser. Mater. Sci. Eng. 308, 012035 (2018).

This study is supported via funding from prince Sattam bin Abdulaziz University Project number (PSAU/2023/R/1445).

Department of Electrical and Electronics Engineering, Cyprus International University, Mersin 10, North Cyprus, Turkey

Management Information System, University of Mediterranean Karpasia, Nicosia, Mersin-10, Turkey

Department of Nuclear and Renewable Energy, Ural Federal University Named After the First President of Russia Boris Yeltsin, 19 Mira Street, Ekaterinburg, Russia, 620002

Department of Electrical Engineering, College of Engineering, Prince Sattam Bin Abdulaziz University, 11942, Al-Kharj, Saudi Arabia

Mohamed F. Elnaggar & Mohammed M. Alrashed

Department of Electrical Power and Machines Engineering, Faculty of Engineering, Helwan University, Hewlan, 11795, Egypt

Department of Electrical Engineering, Faculty of Engineering, Aswan University, Aswan, 81542, Egypt

You can also search for this author in PubMed  Google Scholar

You can also search for this author in PubMed  Google Scholar

You can also search for this author in PubMed  Google Scholar

You can also search for this author in PubMed  Google Scholar

You can also search for this author in PubMed  Google Scholar

You can also search for this author in PubMed  Google Scholar

All authors are equal in contributions.

Correspondence to Mohamed F. Elnaggar.

The authors declare no competing interests.

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Open Access This article is licensed under a Creative Commons Attribution 4.0 International License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons licence, and indicate if changes were made. The images or other third party material in this article are included in the article's Creative Commons licence, unless indicated otherwise in a credit line to the material. If material is not included in the article's Creative Commons licence and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder. To view a copy of this licence, visit http://creativecommons.org/licenses/by/4.0/.

Ishaya, M.M., Adegboye, O.R., Agyekum, E.B. et al. Single-tuned passive filter (STPF) for mitigating harmonics in a 3-phase power system. Sci Rep 13, 20754 (2023). https://doi.org/10.1038/s41598-023-47614-7

DOI: https://doi.org/10.1038/s41598-023-47614-7

Anyone you share the following link with will be able to read this content:

Sorry, a shareable link is not currently available for this article.

Provided by the Springer Nature SharedIt content-sharing initiative

By submitting a comment you agree to abide by our Terms and Community Guidelines. If you find something abusive or that does not comply with our terms or guidelines please flag it as inappropriate.

Scientific Reports (Sci Rep) ISSN 2045-2322 (online)

harmonic filter electrical Sign up for the Nature Briefing newsletter — what matters in science, free to your inbox daily.